西门子PLC编程软件博途(TIA)SCL案例(3)-水处理排泥阀控制

在水处理的沉淀池设计了排泥阀,常用的控制方式是周期排泥,本次简单设计一个8个阀组的周期排泥方式,主要是测试SCL功能。程序的一些保护和复位未设计,只是功能性设计,大家有兴趣可以参阅。

1、设计流程图:

2、时间我们采用总体时间,当计时到达某个范围,程序执行动作。

3、程序设计:

代码:

REGION 初始化

IF NOT #initialize THEN

#Rtsetsec := 10;

#Gtsetsec := 20;

#Cyclesetmin := 60;

END_IF;

#initialize := TRUE;

END_REGION


REGION 阀门自动控制

//计算总的设定时间

#Total_Rtset := #Rtsetsec * 8 + #Gtsetsec * 8;


//运行计时

"R_TRIG_DV1"(CLK := #sec_p,

Q => #p1);

IF #p1 THEN

#Total_Rtview := #Total_Rtview + 1;

END_IF;

//1#阀门开启

IF #DV_remote THEN

IF #Total_Rtview <= #Rtsetsec THEN

#DV_drive1 := 1;

#Cycleviewmin := 0;

ELSE

#DV_drive1 := 0;

END_IF;

//2#阀门开启

IF #Total_Rtview > (#Rtsetsec + #Gtsetsec) AND #Total_Rtview <= (#Rtsetsec * 2 + #Gtsetsec) THEN

#DV_drive2 := 1;

ELSE

#DV_drive2 := 0;

END_IF;

//3#阀门开启

IF #Total_Rtview > (#Rtsetsec * 2 + #Gtsetsec * 2) AND #Total_Rtview <= (#Rtsetsec * 3 + #Gtsetsec * 2) THEN

#DV_drive3 := 1;

ELSE

#DV_drive3 := 0;

END_IF;

//4#阀门开启

IF #Total_Rtview > (#Rtsetsec * 3 + #Gtsetsec * 3) AND #Total_Rtview <= (#Rtsetsec * 4 + #Gtsetsec * 3) THEN

#DV_drive4 := 1;

ELSE

#DV_drive4 := 0;

END_IF;

//5#阀门开启

IF #Total_Rtview > (#Rtsetsec * 4+ #Gtsetsec * 4) AND #Total_Rtview <= (#Rtsetsec * 5 + #Gtsetsec * 4) THEN

#DV_drive5 := 1;

ELSE

#DV_drive5 := 0;

END_IF;

//6#阀门开启

IF #Total_Rtview > (#Rtsetsec * 5 + #Gtsetsec * 5) AND #Total_Rtview <= (#Rtsetsec * 6 + #Gtsetsec * 5) THEN

#DV_drive6 := 1;

ELSE

#DV_drive6 := 0;

END_IF;

//7#阀门开启

IF #Total_Rtview > (#Rtsetsec * 6 + #Gtsetsec * 6) AND #Total_Rtview <= (#Rtsetsec * 7 + #Gtsetsec * 6) THEN

#DV_drive7 := 1;

ELSE

#DV_drive7 := 0;

END_IF;

//8#阀门开启

IF #Total_Rtview > (#Rtsetsec * 7 + #Gtsetsec * 7) AND #Total_Rtview <= (#Rtsetsec * 8 + #Gtsetsec * 7) THEN

#DV_drive8 := 1;

ELSE

#DV_drive8 := 0;

END_IF;

END_IF;

IF #Total_Rtview >=#Rtsetsec *8 + #Gtsetsec * 8 THEN

#P2 := 1;

END_IF;

"R_TRIG_cycle"(CLK := #min_p AND #P2,

Q => #P_cylce);

IF #P_cylce THEN

#Cycleviewmin := #Cycleviewmin + 1;

END_IF;

IF #Cycleviewmin >= #Cyclesetmin THEN

#Total_Rtview := 0;

#P2 := 0;

END_IF;

END_REGION

4、测试:

5、说明

SCL功能中还需增加当DV_remote=false时,所有阀门都不能输出。

另外还有就是过程寄存器数据为0。